PX3-5190NR-M5 Raritan Outlet Metered / Outlet Switched iPDU with Residual Current Monitoring (RCM): 230V, 16A, 8 Outlets (8x C13), No Plug, 1U, LCD Display, 2x USB-A, 1x USB-B, Ethernet, Serial and Sensor Port
(PX-5000 Series) BTO
Description:
Raritan 8 Port 19" Horizontal PDU. Outlet-level Remote Power Management and Control Over IP ( Serial and IP Control PDU with Sensor Feature Port )
The Raritan PX3-5000 family of high-quality rack power distribution units (PDUs) offers real-time remote unit-level and individual outlet-level switching and power monitoring of current (amps), voltage, power (kVA, kW), power factor and energy consumption (kWh) with ISO/IEC +/- 1% billing-grade accuracy. The PX-5000 also supports Raritan’s plug-and-play environmental sensors. Users can define thresholds and receive alerts when thresholds are crossed for both power and environmental events.
Also locking ready capable sockets when used with Raritan's compatible locking cables.
The PX3-5000 series is available in Zero U (vertical mount) and 1U and 2U (horizontal mount) form factors with a wide variety of NEMA, IEC and other plugs and receptacles, including models that support high power distribution such as 400V. Precise power information can be monitored, and the PX-5000 configured, via a user-friendly Web browser GUI or command line interface. Power information is also displayed at the PDU locally. Security is ensured with up to 256-bit encryption, strong passwords and advanced authorization options, including permissions, LDAP/S and Active Directory®. Plus the PX-5000 series is fully compatible with Raritan's Power IQ energy management software solutions.
Raritan PX
Model Number: PX3-5190NR-M5
Features:
Energy Metering Voltage (V), Current (A), Active Power (kW), Real Power (kVA), Energy (kWh), Power Factor
Metering Accuracy ISO/IEC 62053-21 1%
Metering per Input Line Yes
Metering per Branch Circuit Breaker Yes
Metering per Output Receptacle Yes
Remote Outlet Switching Yes
Environmental Sensor Ready Yes
Networking 10/100 BaseT Ethernet. Optional WiFi (802.11a/b/g/n)
Remote Management HTTP(s); SSH; Telnet; RS-232 (Serial); Power IQ; SNMP version v2/v3; SMTP; JSON-RPC
Cascading Yes Max 8 PDUs can be daisy chained using a single Ethernet connection
Onboard Display User-selectable display (voltage, current, or active power:per line, per breaker, or per receptacle)
Compatible Sensors Temperature, Humidity, Air Flow, Static Pressure Single cable connection provides temp/humidity monitoring at three points in cabinet (with a single sensor assembly)
Replaceable controller No
Specification:
PX3-5190NR-M5 Raritan Outlet Metered / Outlet Switched iPDU with Residual Current
(PX-5000 Series)
(BTO) - BUILT TO ORDER
INPUT
Input Plug Cord (230V, Single phase)
Cord Length 3 meters (9.84 feet) standard
Cord Entry Rear feed
Cable Type N/A
Number of Power Cords 1
Maximum Input Current 16A (per line)
Nominal Input Voltage 230V, Single phase
Rated Input Voltage 200 - 240V, Single phase
Input Frequency 50/60Hz
Power Capacity 3.2kVA at 200V, 3.8kVA at 240V
OUTPUT
Nominal Output Voltage 230V
Rated Output Voltage 200 - 240V
Output Connections (8) IEC 60320 C13 2-pole, 3-wire; 10A
Overload Protection N/A
PHYSICAL
Unit Dimensions (W x D x H) 17.3" x 7.2" x 1.7" ; 440mm x 183mm x 44mm
Shipping Dimensions (W x D x H) 16.34" x 12.6" x 22.44" ; 415mm x 320mm x 570mm
Colour Black
Powder coat Mounting 100-89-8430-00
ENVIRONMENTAL
Operating Environment 5 - 60°C (41 - 140°F)
Operating Relative Humidity 5-85%
Operating Elevation 0-10000ft
CONFORMANCE
Regulatory Approvals CE,
Canada ICES-003, Class
A Part 15 Class A of the FCC rules
RoHS compliant